Fire Testing of Omni-Globe Wall & Floor Elements

European Union Standards

EN 1363-1 – Fire Resistance Tests General Requirements

EN 1365-1 – Fire resistance tests for load-bearing elements – Part 1 – Walls

EN 1365-2 – Fire resistance tests for load-bearing elements – Part 2 – Floors and roofs

The Standards stipulate that the specimen tested must satisfy the requirements for 30 minutes

Both Omni-Globe Elements (Wall & Floor) met all requirements for 1 hour 8 minutes.

Well experienced Senior Technician estimated that it would take at least 1.5-2 hours (floor element), and at least 3 hours (wall element), for Omni-Globe Elements to stop satisfying test requirements.

Both tests were stopped after 1 hour and 8 minutes to save costs.

Elevated Floor Element

Test Requirements

  • after 30 minutes the temperature of the top surface must not exceed 140 oC (285 oF)
  • after 30 minutes element must not collapse
  • after 30 minutes deflection at mid-span must not exceed 15 cm (6”)

Results (after 1 hour 8 minutes)

  • temperature on the top of the element remained the same as room temperature
  • element did not collapse
  • element deflection was only 7.5 cm

Note:  After moving the Floor element outside, the 7.5 cm (3”) deflection that developed during testing, has self-straightened.                                                                                 Element has No deformation, or damage (see picture “Floor Element after Fire Test”}.

Vertical Wall Element

Test Requirements

  • after 30 minutes the temperature of the exterior surface must not exceed 140 oC (285 oF)
  • after 30 minutes panel must not collapse

Results (after 1 hour 8 minutes)

  • exterior surface temperature of the element was only slightly higher than room temperature
  • element did NOT collapse